ENVY RT 6~10KVA
ENVY RT 6~10KVA

Specifications
Input | ||
Nominal Voltage | 380/400/415VAC (3Ph+N+PE)or | |
22/230/240VAC(L+N+PE) | ||
Voltage Range | 280~478VAC or 120~276VAC | |
Frequency | 50Hz: 45~55Hz/ 60Hz: 54~66Hz | |
(Auto sensing) | ||
Power Factor | ≥0.99 | |
Bypass Voltage Range | Max.voltage:220V: +25% | |
(Optional +10%, +15%, +20%) | ||
230V: +20% (Optional +10%, 15%) | ||
240V: +15% (Optional +10%) | ||
Min. Voltage: -45% | ||
(Optional -20%, -30%) | ||
Frequency | ±10% | |
THDi | Load<100%(Linear load), | |
Load5%(Non-linear load) | ||
Generator Input | Support | |
Output | ||
Rating Voltage | 220 / 230 / 240 VAC | |
Power Factor | 0.9 | |
Voltage Regulation | ±1% | |
Frequency | 1.Line mode: ±1%/±2%/±4%/±5%/ | |
±10% of the rated frequency(Optional) | ||
2.Battery mode: 50/60Hz±0.1 | ||
Crest Factor | 3:1 | |
THDv | Load<2% (Linear load) | |
Load<5% (Non-linear load) | ||
Efficiency | ≥93.5% | |
Battery Bank (MP-BR Battery Bank Series) | ||
Capacity | 6KVA | 10KVA |
Battery Type & Max. Quantity | 7AHx20 | 9AHx20 |
Battery Bank Diemensions | 720x443x131(3U) | 720x443x131(3U) |
(WxDxH)(mm) | ||
Net Weight (kg) | 56 | 62 |
Model/Capacity | ||
Models | ENVY RT | |
Rating Capacity | 6KVA | 10KVA |
Rating Power | 6k/5.4k | 10k/9k |
System Features | Mains to Battery: 0ms, Mains to Bypass: 0ms | |
Transfer time | Load<110%, 60 mins, Load<125%, 30 mins, | |
Load<150%, last 1 min, Load>150%, turn to | ||
bypass mode | ||
Bypass Mode | ENVY RT 6KVA: 40A Input Breaker | |
ENVY RT 10KVA: 60A Input Breaker | ||
Short Circuit | Hold whole system | |
Overheat | Line mode: Turn to bypass, | |
Backup mode: Shut down UPS immediately | ||
Low Battery Voltage | Alarm and Switch off | |
Self-diagnostics | Upon power ON and software control | |
Battery | Advanced battery management | |
Audible & Visual Alarms | Line failure, Battery low, Overload & System fault | |
Status LED/LCD Display | Line failure, Battery low, Overload & | |
Audible & Visual | Line failure, Battery low, Overload & System fault | |
Status LED & LCD | Line mode, Battery mode, ECO mode, Bypass | |
mode, Battery low, Battery bad, Overload & UPS fault | ||
Reading on the LCD Display | Input voltage, Input frequency, Output voltage, | |
Output frequency, Load percentage, Battery | ||
voltage, Inner temperature & Remaining battery | ||
backup time | ||
Communication Interface | RS232, USB, SNMP card (Optional) & Relay card (Optional) |